朱金婵, 张小波, 杨锡清, 等. 基于压缩波束形成的电力设备表面放电声学定位方法[J]. 高电压技术, 2026,52(7):3360-3371.
ZHU Jinchan, ZHANG Xiaobo, YANG Xiqing, et al. 基于压缩波束形成的电力设备表面放电声学定位方法[J]. 2026, 52(7): 3360-3371.
朱金婵, 张小波, 杨锡清, 等. 基于压缩波束形成的电力设备表面放电声学定位方法[J]. 高电压技术, 2026,52(7):3360-3371. DOI: 10.13336/j.1003-6520.hve.20251209.
ZHU Jinchan, ZHANG Xiaobo, YANG Xiqing, et al. 基于压缩波束形成的电力设备表面放电声学定位方法[J]. 2026, 52(7): 3360-3371. DOI: 10.13336/j.1003-6520.hve.20251209.
电力设备表面放电是潜伏性故障或早期缺陷的重要征兆,基于麦克风阵列的声学检测手段可无接触式地捕捉设备放电辐射的声信号,借助阵列信号处理算法可实现对放电声源的定位。然而,传统算法定位精度差、鲁棒性不足。对此,提出了一种基于压缩波束形成(compressive beamforming
CSBF)的设备表面放电定位算法,首先建立广义高斯分布变体函数约束的压缩波束形成定位模型,然后基于加速近端梯度(accelerate proximal gradient
APG)框架高效求解模型,获得放电声源数量和坐标的估计结果。为了验证所提方法的有效性,在不同声源间距、观测环境和复杂度参数设置下进行了一系列仿真,并在实验室环境中开展铜丝电晕、缺陷绝缘子放电定位实验;结果表明:CSBF-APG对声源位置的估计误差小于0.1 m,平均运行时间小于2 s,具有良好的分辨率和鲁棒性,且对存在反射和混响的工程环境具备一定适应性。最后,在某换流变感应耐压局放试验中,借助论文方法,成功快速定位到试验设备的异常放电声源,提高了试验效率,验证了论文方法的有效性和实用性,可为电力设备表面放电声学检测和定位提供指导和参考。
Surface discharge of power equipment is an important indicator of latent faults and early defects. The microphone array-based acoustic detection method can acquire the discharging acoustic signals emitted by the equipment in a non-contact manner
and then the discharge position can be localized by array signal processing algorithms. However
conventional algorithms suffer from low resolution and poor robustness. To overcome these shortages
an acoustic localization method for surface discharge of power equipment based on compressive beamforming (CSBF) is proposed in this paper. First
the localization problem is formulated as a CSBF model constrained by a variant function of the generalized Gaussian distribution. Then
the model is solved efficiently based on the accelerated proximal gradient (APG) framework
and the estimated results of source counts and positions are obtained. To demonstrate the effectiveness of the proposed method
a series of simulations with different source distances
environmental observation conditions
and computational parameters are conducted; furthermore
the copper wire and defective insulator discharging localization experiments are carried out in the laboratory environment. Results show that CSBF-APG can achieve a position estimated error of less than 0.1 meter and the running time of less than 2 seconds
which demonstrates its favorable resolution and robustness
and also exhibits adaptability to practical engineering environments with reflections and reverberation. Finally
in a converter transformer high-voltage partial discharge test
the proposed method is adopted to successfully locate the discharge source of an experimental grounding wire
improving the test efficiency and also verifying its practicality. This paper can provide valuable guidance and reference for acoustic detection and localization of surface discharges of power equipment.