为了提高直流输电系统受端电流源可控换相换流器(controllable line commutated converter,CLCC)对交流系统的无功支撑能力,针对该可控换相换流器提出无功支撑控制策略。首先介绍了可控换相换流器抵御换相失败的工作原理,理论分析了可控换相换流器无功功率随触发角和交流电压的变化特性,理论上验证了通过调节触发角可以调节换流器的无功功率。然后在传统电流源换流器控制策略的基础上提出无功支撑控制策略,并分析了其控制逻辑的合理性。最后介绍了CLCC数字物理混合动模平台,在该平台上开展了控制策略验证试验。试验结果表明:所提出的无功支撑控制策略可以让换流器在三相故障交流电压跌落50%时吸收的无功功率减小到零,让换流站(换流器+滤波器)向系统释放0.16 pu的无功。这加快了受端交流电压的恢复,并且减小了直流电压、直流电流和有功功率的暂态波动。其中直流电压波动范围由0.45~0.97 pu缩小到0.647~0.97 pu,直流电流波动范围由0.59~1.43 pu缩小到0.73~1.3 pu,换流站有功功率波动范围由0.375~0.86 pu缩小到0.647~0.86 pu。在单相故障下,所提出的无功支撑控制策略并未加快交流电压恢复和减小有功功率波动。论文所提出的控制策略可为可控换相换流器工程控制策略提供参考。
To improve the reactive power support capability of the current source controllable line commutated converter (CLCC) applied at the receiving end of a DC transmission system for a AC system
a reactive power support control strategy is proposed specifically for this CLCC. Firstly
the operation principle of CLCC against commutation failure is introduced. The reactive power characteristics of the CLCC in relation to firing angle and AC voltage were theoretically analyzed. The results verify that the converter's reactive power can be regulated by adjusting the firing angle. Based on the conventional line commutated converter control strategy
a reactive power support control strategy is proposed
and the rationality of its control logic is analyzed. Finally
the digital-physical hybrid dynamic model platform for CLCC was introduced
and validation tests of the control strategy were conducted on this platform. The experimental results demonstrate that the proposed reactive power support control strategy can reduce the reactive power absorbed by the converter to zero during a three-phase fault when the AC voltage drops by 50%
while enabling the converter station (converter and filters) to inject 0.16p.u. of reactive power into the system. This accelerates the recovery of the receiving-end AC voltage and reduces the transient fluctuations in DC voltage
DC current
and active power. Specifically
the fluctuation range of DC voltage is reduced from 0.45~0.97 pu to 0.647~0.97 pu
the DC current fluctuation range is narrowed from 0.59~1.43 pu to 0.73~1.3 pu
and the active power fluctuation range of the converter station is compressed from 0.375~0.86 pu to 0.647~0.86 pu. Under a single-phase fault
the proposed reactive power support control strategy does not accelerate AC voltage recovery or reduce the magnitude of the active power dip. The control strategy proposed in this paper can provide a valuable reference for the engineering control strategies of CLCC.