厉璇, 刘永慧, 赵月杭, 等. 基于电压源等效的构网型储能变流器幅值饱和限流模式暂态稳定性分析[J]. 高电压技术, 2026,52(5):2172-2184.
LI Xuan, LIU Yonghui, ZHAO Yuehang, et al. 基于电压源等效的构网型储能变流器幅值饱和限流模式暂态稳定性分析[J]. 2026, 52(5): 2172-2184.
厉璇, 刘永慧, 赵月杭, 等. 基于电压源等效的构网型储能变流器幅值饱和限流模式暂态稳定性分析[J]. 高电压技术, 2026,52(5):2172-2184. DOI: 10.13336/j.1003-6520.hve.20251565.
LI Xuan, LIU Yonghui, ZHAO Yuehang, et al. 基于电压源等效的构网型储能变流器幅值饱和限流模式暂态稳定性分析[J]. 2026, 52(5): 2172-2184. DOI: 10.13336/j.1003-6520.hve.20251565.
在新型电力系统中,构网型储能变流器为新能源机组提供了可靠的故障穿越能力支撑。其限流控制在抑制变流器暂态过流的同时恶化了暂态稳定性。传统对于幅值饱和限流的构网变流器暂态稳定性分析,多基于电流源等效模型,其难以揭示限流期间变流器运行模式切换带来的物理意义变化,也难以分析电压控制策略和限流环节对变流器稳定性的影响机理。针对该问题,提出了一种基于电压源等效模型的变流器幅值饱和限流模式暂稳性分析方法。从等效系统阻抗的角度,分析了不同优先级幅值饱和限流策略对暂态功角特性和稳定性的影响机理。分析结果表明,采用虚拟导纳电压内环的构网变流器,幅值饱和限流环节通过调节系统阻抗模和阻抗角实现电流限幅与相位偏转,其中阻抗角通过抬升或压低限流期间功率特性曲线来主导影响系统的暂态稳定裕度。比较结果显示,采用q轴优先限流策略的变流器具备最大的系统阻抗角和暂态稳定裕度,采用d轴优先限流策略的阻抗角和暂稳裕度最小。仿真结果验证了所提电压源等效模型的准确性和理论分析的正确性。
Grid-forming voltage source converters (GFM-VSCs) offer reliable supports for the fault ride-through capability of renewable energy generators. While current-limiting (CL) control degrades the system’s transient stability during the fault. Traditional transient stability analysis for GFM-VSCs with amplitude-saturated current limiters predominantly relies on the current-source equivalent models. Such models not only fail to reveal changes in physical meaning induced by the mode switching during CL
but also struggle to analyze the influence mechanism of voltage control schemes and current limiters on transient stability. To address this issue
a transient stability analysis method for GFM-VSCs with current limiters is proposed based on the voltage-source equivalent model. From the perspective of equivalent system impedance
the influence mechanism of current limiters with different priorities on the power characteristics and system stability is systematically analyzed. The results show that
for GFM-VSCs with virtual admittance voltage control
the current limiters realize current suppression and phase shift by adjusting the magnitude and angle of the system impedance. Specifically
the impedance angle plays a dominant role in affecting the transient stability margin
by elevating or depressing the power characteristic during CL. Comparative analysis shows that the converter with the q-axis priority current limiters exhibits the largest impedance angle and stability margin
whereas the converter with the d-axis priority limiters has the smallest ones. Simulation results validate the accuracy of the proposed model and the correctness of the theoretical analysis.