杨晓宇, 邱宁, 李晓昂, 等. GIS外施激振耐压试验方法及对潜伏性异物检测有效性研究[J]. 高电压技术, 2026,52(5):2131-2138.
YANG Xiaoyu, QIU Ning, LI Xiaoang, et al. GIS外施激振耐压试验方法及对潜伏性异物检测有效性研究[J]. 2026, 52(5): 2131-2138.
杨晓宇, 邱宁, 李晓昂, 等. GIS外施激振耐压试验方法及对潜伏性异物检测有效性研究[J]. 高电压技术, 2026,52(5):2131-2138. DOI: 10.13336/j.1003-6520.hve.20251454.
YANG Xiaoyu, QIU Ning, LI Xiaoang, et al. GIS外施激振耐压试验方法及对潜伏性异物检测有效性研究[J]. 2026, 52(5): 2131-2138. DOI: 10.13336/j.1003-6520.hve.20251454.
通过传统静态耐压试验的超/特高压金属封闭组合电器(gas insulated switchgear,GIS)在开关操作过程中多次发生异物诱发放电故障,反映了传统静态耐压试验对潜伏性异物缺陷检测的局限性。为此提出了GIS外施激振耐压试验新方法和流程,在GIS耐压试验过程中外施机械振动,以期激发和增强潜伏性金属异物运动并实现高效检出,进一步,构建了550 kV真型GIS的外施激振耐压试验平台,并针对法兰狭缝潜藏、屏蔽罩潜藏及高密度异形等3类典型的潜伏性异物缺陷,研究试验新方法对缺陷的检测有效性。结果表明,潜伏性金属微粒缺陷在阶梯型静态试验电压下呈“静态蛰伏”状态,无超声、无局放、无击穿,难以有效检出;紧随其后,进行外施激振耐压试验,潜伏性金属微粒呈“脱陷”状态,且在不同电压阶梯下呈现间歇跳跃或持续舞动等运动状态,超声局放信号显著增强。据此,验证了GIS外施激振耐压试验对潜伏性金属微粒的检测有效性,为提升GIS设备绝缘可靠性提供了一种简单高效的绝缘试验新方法。
The occurrence of foreign object-induced discharge faults during switching operations of ultra/high-voltage gas-insulated switchgear (GIS) tested by conventional static withstand voltage tests can reflect the limitations of detecting latent foreign object defects by traditional static withstand voltage tests. This paper presents a novel method and procedure for conducting seismic endurance tests on GIS. Mechanical vibrations are externally applied during the GIS endurance test process
aiming to stimulate and enhance the movement of latent metal foreign objects to achieve efficient detection. Furthermore
a test platform for external excitation and vibration resistance was established for a 550 kV real-type GIS. This platform was used to investigate the effectiveness of a new testing method for detecting hidden defects such as flange gap concealment
shield cover concealment
and high-density irregularities. The results indicate that latent metal particle defects exhibit a “static dormant” state under stepped static test voltages
and neither ultrasound or partial discharge or breakdown occurs
making them difficult to detect effectively. Subsequently
during external vibration endurance tests
the latent metal particles show a “release” state
displaying intermittent jumping or continuous dancing movements under different voltage steps
and ultrasound and partial discharge signals significantly increase. This validates the effectiveness of the GIS external vibration withstand test in detecting latent metal particles
offering a simple and efficient insulation testing method to enhance the insulation reliability of GIS equipment.