1. 电网环境保护全国重点实验室,武汉,430072
2. 武汉大学电气与自动化学院,武汉,430072
3. 中国电建集团中南勘测设计研究院有限公司,长沙,410014
收稿:2026-06-30,
纸质出版:2026
移动端阅览
王跃新, 杜志叶, 李根, 等. 柔直换流站500kV高压电缆异常放电与发热现象仿真研究[J]. 高电压技术, 2026,52(6):2929-2939.
WANG Yuexin, DU Zhiye, LI Gen, et al. 柔直换流站500kV高压电缆异常放电与发热现象仿真研究[J]. 2026, 52(6): 2929-2939.
王跃新, 杜志叶, 李根, 等. 柔直换流站500kV高压电缆异常放电与发热现象仿真研究[J]. 高电压技术, 2026,52(6):2929-2939. DOI: 10.13336/j.1003-6520.hve.20250986.
WANG Yuexin, DU Zhiye, LI Gen, et al. 柔直换流站500kV高压电缆异常放电与发热现象仿真研究[J]. 2026, 52(6): 2929-2939. DOI: 10.13336/j.1003-6520.hve.20250986.
柔直换流站紧凑化建设为目前的发展趋势,其电缆夹层中高压电缆的敷设也更为紧密,导致内部电磁环境越发复杂,异常放电与发热故障风险不断提高。为此,以国内一起柔直换流站内500 kV高压电缆出现的异常放电与发热故障现象为研究对象,提出了一种考虑异常谐波的电缆电磁-热耦合仿真分析方法,构建了石墨导电涂层(graphite conductive coating,GCC)涂覆条件下的电缆电磁-热耦合仿真模型,结合场路耦合理论开展GCC存在多接地点工况下的异常放电与发热仿真研究,明确了工程上产生异常放电与发热现象的主要原因,给出了优化GCC涂覆厚度的电缆多点接地缓解措施。研究结果表明:线路中异常谐波含量和GCC上的额外接地点是导致电缆出现异常放电与发热现象的主要原因,故障相电缆GCC干扰电压最高达到461.30 V,电缆温度最高达到149.94 ℃。经过缓解设计后,故障相电缆GCC干扰电压下降62.25%,电缆最高温度下降73.52%。研究成果可为工程上电缆异常放电与发热现象的仿真计算以及缓解设计提供有益参考。
Compact construction has become a development trend for flexible direct current converter stations. High-voltage cables in cable interlayers are arranged more tightly
resulting in an increasingly complex electromagnetic environment and a higher risk of abnormal discharge and heating faults. Therefore
the abnormal discharge and heating phenomena of 500 kV high-voltage cables in a flexible direct-current converter station in China are taken as the research object. A cable electromagnetic-thermal coupling simulation and analysis method considering abnormal harmonics is proposed. A cable electromagnetic-thermal coupling simulation model under graphite conductive coating (GCC) conditions is constructed. Based on the field-circuit coupling theory
abnormal discharge and heating under multiple grounding points on the GCC are simulated
the main causes of the engineering phenomena are clarified
and a multi-point grounding mitigation design with optimized GCC coating thickness is then developed. The results show that abnormal harmonic contents in the line and additional grounding points on the GCC are the main causes of abnormal discharge and heating in the cable. The maximum GCC interference voltage of the faulty-phase cable reaches 461.30 V
and the maximum cable temperature reaches 149.94 ℃. After the mitigation design
the GCC interference voltage of the faulty-phase cable decreases by 62.25%
and the maximum cable temperature decreases by 73.52%. The research results can provide a useful reference for simulation and mitigation of cable abnormal discharge and heating phenomena in engineering applications.
0
浏览量
2
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621