胡钰骁, 李江涛, 张文娇, 等. 柔性高压直流双极带金属回线系统电缆电磁暂态建模与极线故障特性[J]. 高电压技术, 2025,51(10):5003-5013.
HU Yuxiao, LI Jiangtao, ZHANG Wenjiao, et al. 柔性高压直流双极带金属回线系统电缆电磁暂态建模与极线故障特性[J]. 2025, 51(10): 5003-5013.
胡钰骁, 李江涛, 张文娇, 等. 柔性高压直流双极带金属回线系统电缆电磁暂态建模与极线故障特性[J]. 高电压技术, 2025,51(10):5003-5013. DOI: 10.13336/j.1003-6520.hve.20250845.
HU Yuxiao, LI Jiangtao, ZHANG Wenjiao, et al. 柔性高压直流双极带金属回线系统电缆电磁暂态建模与极线故障特性[J]. 2025, 51(10): 5003-5013. DOI: 10.13336/j.1003-6520.hve.20250845.
交联聚乙烯(cross-linked polyethylene,XLPE)绝缘电缆作为柔性直流系统的重要传输设备,受系统各类暂态事件的影响,其绝缘长期承受暂态电应力以致逐渐劣化。为提升高压电缆暂态计算精度,该文提出考虑电缆多层结构与材料特性的分布参数等效电路解析算法;基于此,在PSCAD/EMTDC软件中搭建了柔性高压直流双极带金属回线系统,分析了直流极线故障暂态电压、电流形成机理及电缆极线与金属回线的暂态特性,深入讨论了长距离传输下的电缆故障暂态特性变化。研究表明,故障电缆极线的非故障位置将出现过零阻尼振荡波,其伪周期分布与故障距离及波速度相关,其振荡幅值与故障距离、故障阻抗、阀侧阻抗、电缆特征阻抗及衰减特性相关,振荡所导致的反向电压峰值随着离故障点距离的增加而增大,最大值接近-1 pu(基准值320 kV)。同时,极线故障将导致故障极与金属回线产生幅值相近的较高过电流水平,电流幅值取决于MMC闭锁后不控整流稳态阶段及交流断路器的跳闸时间,直流极线首端接地故障所导致的电流峰值最高。短电缆线路(千米级)面临更大的故障极电缆与金属回线暂态电流,长电缆线路(百千米级)面临更严重的金属回线过电压与单极故障时健康极电缆过电压问题。研究结果旨在为柔性直流系统中电缆暂态电应力的评估与绝缘配合提供准确的电缆模型与仿真数据参考。
As a key transmission device in voltage source converter (VSC)-based high-voltage direct current (HVDC) system
cross-linked polyethylene (XLPE) cables are affected by various transient events. The long-term exposure to transient electrical stress can lead to gradual insulation degradation. To improve the accuracy of the transient calculation
an analytical method for determining the equivalent distributed circuit parameters of cable was proposed after the multilayer structure and the material properties were considered. Based on the proposed model
a VSC-HVDC bipolar system with metallic return was modeled in PSCAD/EMTDC to study the mechanisms of overvoltage and overcurrent under the pole-to-ground fault. Transient characteristics of both pole and metallic return cables were obtained
with an in-depth investigation into the variations of fault-induced transients under long-distance transmission scenarios. The results show that
under a pole-to-ground fault
a zero-crossing damped oscillation will appear at the non-fault section of the faulty cable. The pseudo-period of the oscillation is related to the fault distance and wave velocity
while the oscillation amplitude is influenced by the fault distance
fault impedance
valve-side impedance
cable characteristic impedance
and attenuation characteristics. The reverse voltage peak caused by the oscillation increases with distance from the fault point
reaching a maximum value close to -1 pu (base value 320 kV). Pole-to-ground faults can lead to similar and significant overcurrent in both the faulty pole and the metallic return cable. The peak overcurrent is determined by the uncontrolled rectification steady-state stage after MMC blocking and the trip time of the AC circuit breaker. A grounding fault at the sending end of the DC cable results in the highest current peak. Short cable routes (kilometer scale) experience larger transient currents
while long cable routes (hundred-kilometer scale) are more prone to severe overvoltage in the metallic return cable and the healthy pole during single-pole faults. The study aims to provide an accurate cable model and simulation reference for evaluating transient electrical stresses and insulation coordination for cables in VSC-HVDC system.