Polymer superhydrophobic coating is one of the effective strategies to solve the icing problem of transmission lines icing and insulator wet flashover; however
it is difficult for the low hydrophobicity of pure polymer to meet the needs of transmission lines anti-icing and insulator anti-wet flashover. Therefore
amorphous silica was formed by co-hydrolysis of tetraethyl silicate
and fluorinated silica (SiO2@F) was successfully anchored on the surface of the substrate to prepare a superhydrophobic coating with high insulation performance. Under optimal loading conditions
the coating exhibits excellent superhydrophobic properties
with a contact angle of 165.1°
and a sliding angle of 0.3°. After undergoing UV radiation
salt spray corrosion
rainwater erosion
sandpaper abrasion
and ultra-low temperature testing
the coating still maintains excellent superhydrophobicity. Additionally
the wet flashover strength of the coating is 74.26% higher than that of room-temperature vulcanized silicone rubber (RTV) coating
which improves the insulation performance of insulators. Finally
the superhydrophobic properties of the polymer coating were verified on different substrates
proving the universality of the polymer coating. In summary
the superhydrophobic coating studied in this paper provides new insights for the design of new materials for anti-icing applications in power transmission lines.