韩兴波, 袁路强, 张衡, 等. 复合绝缘子单个伞裙结构对覆冰过程水滴运动碰撞的影响机制[J]. 高电压技术, 2026,52(3):1395-1404.
HAN Xingbo, YUAN Luqiang, ZHANG Heng, et al. 复合绝缘子单个伞裙结构对覆冰过程水滴运动碰撞的影响机制[J]. 2026, 52(3): 1395-1404.
韩兴波, 袁路强, 张衡, 等. 复合绝缘子单个伞裙结构对覆冰过程水滴运动碰撞的影响机制[J]. 高电压技术, 2026,52(3):1395-1404. DOI: 10.13336/j.1003-6520.hve.20250154.
HAN Xingbo, YUAN Luqiang, ZHANG Heng, et al. 复合绝缘子单个伞裙结构对覆冰过程水滴运动碰撞的影响机制[J]. 2026, 52(3): 1395-1404. DOI: 10.13336/j.1003-6520.hve.20250154.
输电线路绝缘子覆冰闪络防治一直是电网防冰减灾的重点工作,通过优化复合绝缘子伞裙结构进而降低复合绝缘子覆冰速率是有效的防冰方法之一。基于流体力学基本理论,根据空气中液态水含量和水滴中值体积直径等参数推导了水滴间距计算式,通过批量式发射跟踪覆冰过程中复合绝缘子外部水滴运动轨迹获得复合绝缘子伞裙表面的水滴碰撞分布和效率。以复合绝缘子单伞裙为研究对象,进一步数值分析了不同环境参数和伞裙结构参数对水滴运动碰撞的影响规律,并进行了自然覆冰验证试验。结果表明:影响覆冰期间复合绝缘子对过冷却水滴捕获速率的关键结构参数为伞裙直径和上下倾斜角,关键环境参数为风速和水滴中值体积直径;复合绝缘子伞裙直径越小,伞裙的整体水滴碰撞系数α1越大;上倾斜角越小的复合绝缘子伞裙越容易形成覆冰,但在严重覆冰条件下,伞裙上倾斜角越小越有利降低伞裙的水滴捕获效率和覆冰冻结速率。自然覆冰条件下,相对于上倾斜角较大的复合绝缘子伞裙,上倾斜角较小的复合绝缘子覆冰速率更低。伞裙直径越小,覆冰质量越小,但更易被覆冰桥接。
The prevention and control of icing flashover on transmission line insulators has always been a key task in power grid ice disaster prevention and mitigation. Optimizing the shed structure of composite insulators to reduce the icing rate is one of the effective anti-icing methods. Based on the fundamental theory of fluid mechanics
this paper derives a formula for calculating the spacing of water droplets based on parameters such as the liquid water content in the air and the median volume diameter of droplets. By batch-emitting and tracking the trajectories of water droplets out of composite insulators during the icing process
the distribution and collision efficiency of water droplets on the insulator sheds are obtained. By taking a single shed of a composite insulator as the research object
the influence of different environmental and structural parameters on the collision of water droplets is numerically analyzed
and natural icing verification tests are conducted. The results show that the key structural parameters affecting the capture rate of supercooled water droplets by composite insulators during icing are the shed diameter and the upper and lower inclination angles
while the key environmental parameters are wind speed and the median volume diameter of water droplets. The smaller the shed diameter of the composite insulator is
the greater the overall water droplet collision coefficient α1 will be. Sheds with smaller upper inclination angles are more prone to icing; however
under severe icing conditions
smaller upper inclination angles are more beneficial for reducing the water droplet capture efficiency and icing rate. Under natural icing conditions
composite insulator sheds with smaller upper inclination angles have a lower icing rate compared to those with larger upper inclination angles. The smaller the shed diameter is
the less the icing mass is
but the more easily the shed is bridged by ice. The conclusions of this paper provide technical references for the optimization and design of anti-icing structures for composite insulator sheds.