The trapped charge voltage during a gas insulated switchgear (GIS) disconnector operation significantly influences the characteristics of the very fast transient overvoltage (VFTO)
such as its amplitude and waveform
and in-depth study of its variation law is essential for accurately characterizing VFTO. Consequently
using an ultra-high voltage GIS as a prototype
we derived the relationship between trapped charge voltage
disconnector speed
and breakdown voltage polarity via mathematical description of repeated breakdown processes. An arc model for disconnector multiple restrikes
considering the polarity effect of gap breakdown voltage
was established
and its accuracy was verified by comparison with measured waveforms of the IEC typical test circuit. Based on this model
the influences of switch speed and polarity characteristics on trapped charge voltage variation laws were studied by simulation
and the impact of trapped charge voltage on VFTO waveform and amplitude during repeated breakdown was further analyzed. The results indicate that a higher operating speed leads to an elevated trapped charge voltage level
consequently resulting in an increased VFTO magnitude; trapped charge voltage exhibits different variation laws with the positive-to-negative breakdown voltage ratio
so the maximum VFTO during operation does not necessarily occur in the last opening or first closing breakdown. When the ratio is large
trapped charge voltage amplitude is small; when approaching 1
the most severe breakdown conditions may occur during both opening and closing operations. Thus
increasing the ratio can reduce the trapped charge voltage amplitude