电容式电压互感器(capacitor voltage transformer,CVT)的等效电路存在高频响应误差大、结果偏离度高的问题。为此,以500 kV CVT为研究对象,通过试验和仿真方法,开展了CVT各组件和结构的高频等值电路参数化研究,建立计及寄生参数下CVT的高频等效电路模型,计算CVT的传递函数,分析CVT暂态耦合电容的传递特性,讨论寄生参数对暂态耦合电容频响特性的影响。研究得到,所提高频等效电路模型使得CVT频响幅值和相角在高频激励下误差分别减小了106.2%和49.4%,CVT暂态耦合电容寄生电感增大会使得传递曲线尖峰值和低谷值频率降低但幅值增大,相位点频率分布误差出现低频化。研究结果有助于认识雷电和操作过电压下CVT的高频响应特性。
Abstract
The equivalent circuit for capacitive voltage transformer (CVT) exhibits significant high-frequency response errors and substantial deviation in results. To address this issue
a comprehensive study was conducted on a 500 kV CVT
utilizing both experimental and simulation methods. This study involved parameterizing the equivalent circuit of each component and structure of CVT
developing a high frequency equivalent circuit model that includes parasitic parameters. The transfer function of the CVT was calculated
and the transient coupling capacitance was analyzed for its transfer characteristics. The impact of parasitic parameters on the frequency response characteristics of the transient coupling capacitance was also discussed. The research findings indicate that the proposed high frequency equivalent circuit model reduced the amplitude and phase angle errors of the CVT frequency response under high-frequency excitations by 106.2% and 49.4%
respectively. It was also observed that an increase in the parasitic inductance of the CVT’s transient coupling capacitance leads to a decrease in the frequency of the peaks and troughs of the transfer curve
while increasing their amplitude. Additionally
the frequency distribution error of the phase points shifts to lower frequencies. The results help to understand the high frequency response characteristics of CVT under lightning and operating overvoltage.